  4. use the specified size of crimp terminals (m3.5 screws) to wire the terminal block. t ighten the screws on the terminal block using the tightening torque within the range of 1.2 n.m. 5. do not connect anything to unused terminals. emc guidelines: 1. use proper input power cables with shortest connections and twisted type. 2. layout of connecting cables shall be away from any internal emi source. all safety related codifications, symbols and instructions that appear in this operating manual or on the equipment must be strictly followed to ensure the safety of the operating personnel as well as the instrument. if the equipment is not handled in a manner specified by the manufacturer it might impair the protection provided by the equipment. read complete instructions prior to installation and operation of the unit. w arning: risk of electric shock. load connections 1. the service life of the output relays depends on the switching capacity and switching conditions. consider the actual application conditions and use the product within the rated load and electrical service life. 2. although the relay output is rated at 10 amps it is always necessary to use an interposing relay or contactor that will switch the load. this avoids damage to the controller in the event of a fault short developing on the power output circuit. 3. always use a separate fused supply for the power load circuit and do not take this from the live and neutral terminals supplying power to the controller . 3. circuit breaker or mains switch must be installed between power source and supply terminals to facilitate power 'on' or off  function. however this switch or breaker must be installed in a convenient position normally accessible to the operator . 4. use and store the temperature controller within the specified ambient temperature and humidity ranges as mentioned in this manual. wiring guidelines w arning: 1. t o p r e v e n t t h e r i s k o f e l e c t r i c s h o c k p o w e r s u p p l y t o t h e e q u i p m e n t m u s t b e k e p t o f f w h i l e d o i n g t h e w i r i n g a r r a n g e m e n t . d o n o t t o u c h t h e t e r m i n a l s w h i l e p o w e r i s b e i n g s u p p l i e d . 2. t o eliminate electromagnetic interference use short wire with adequate ratings; twists of the same in equal size shall be made. for the input and output signal lines, be sure to use shielded wires and keep them away from each other . 3. cable used for connection to power source, must have a 2 cross section of 1mm or greater . these wires shall have insulation capacity made of at least 1.5kv . 4. when extending the thermocouple lead wires, always use thermocouple compensation wires for wiring. for the r td type, use a wiring material with a small lead resistance (5 ? max per line) and no resistance dif ferentials among three wires. 5. a better anti-noise ef fect can be expected by using standard power supply cable for the instrument. maintenance 1 the equipment should be cleaned regularly to avoid blockage of ventilating parts. 2. clean the equipment with a clean soft cloth . do not use isopropyl alcohol or any other cleaning agent. 1. when powering up for the first time, disconnect the output connections. 2. fuse protection: the unit is normally supplied without a power switch and fuses. make wiring so that the fuse is placed between the mains power supply switch and the controller . (2 pole breaker fuse- rating: 275v ac,1a for electrical circuitry is highly recommended) 3. since this is a built-in-type equipment (finds place in main control panel), its output terminals get connected to host equipment. such equipment shall also comply with basic e m i / e m c a n d o t h e r s a f e t y r e q u i r e m e n t s l i k e b s e n 6 1 3 2 6 - 1 a n d b s e n 6 1 0 1 0 r e s p e c t i v e l y . 4. thermal dissipation of equipment is met through ventilation holes provided on chassis of equipment. such ventilation holes shall not be obstructed else it can lead to a safety hazard. 5. the output terminals shall be strictly loaded to the manufacturer specified values/range. electrical precautions during use electrical noise generated by switching of inductive loads can create momentary disruption, erratic display , latch up, data loss or permanent damage to the instrument. t o reduce noise: a) use of snubber circuits across loads as shown above, is recommended. b) use separate shielded wires for inputs. safety precautions inst alla tion guidelines 1. this equipment, being built-in-type, normally becomes a part of main control panel and in such case the terminals do not remain accessible to the end user after installation and internal wiring. 2 do not allow pieces of metal, wire clippings, or fine metallic fillings from installation to enter the product or else it may lead to a safety hazard that may in turn endanger life or cause electrical shock to the operator . 1. prepare the panel cutout with proper dimensions as shown above. 2. remove the clamp from the controller and push the controller into the panel cutout. insert the clamp from the rear side until the main unit is securely fit into the panel. 3. the equipment in its installed state must not come in close proximity to any heating sources, caustic vapors, oils, steam, or other unwanted process by-products. mechanical inst alla tion n l c no tc lo a d r c tc snubber mov tc tc n l snubber c no r c contactor lo ad c mov f o r l o a d c u r r e n t l e s s t h a n 0 . 5 a f o r b i g g e r l o a d s , u s e i n t e r p o s i n g r e l a y / c o n t a c t o r outline dimensions (in mm) panel cutout dimensions (in mm) specifica tions display 3 + 3 digit, 7 segment digital display led indications r: control output on keys 3 keys for digital setting input specifica tions input signal thermocouple (j,k,t ,r,s) / r td (pt100) sampling time 250 ms input filter (ftc) 0.2 to 10.0 sec resolution o fixed 1 resolution t emperature unit o c / f selectable indication accuracy f or tc inputs: 0.25% of fs 1 for r & s inputs: 0.5% of f .s 2 (20 min of warm up time for tc inputs) f or r td inputs : 0.1% of fs 1 functional specifications control method 1) pid control with auto tuning2) on-off control proportional band (p) 1 to 400 integral t ime (i) 0.0 to 99.9 min derivative t ime (d) 0 to 999 sec cycle t ime 0.1 to 99.9 sec hysteresis width 0.1 to 99.9 manual reset v alue -19.9 to 19.9 control output (relay or ssr user selectable) relay contact (spdt) 10 a @ 250v ac / 30v dc, resistive ssr drive output (v oltage pulse) 12v dc, 50 ma power suppl y supply v oltage 85 to 270v ac/dc (ac: 50 or 60 hz ) optional - 24v ac/dc power consumption 5 v a max @230v ac t emperature operating : 0 to 50 c ; storage : -20 to 75 c humidity (non-condensing) 95% rh w eight tc533ax: 129 gmstc233ax: 180 gms tc333ax: 240 gms o p e ra ti n g /1 1 0 3 / t c 5 3 3 a x / t c 2 3 3 a x / t c 3 3 3 a x / o p 2 9 3 -v 0 4 (p a g e 1 o f 3 ) a 52 72 96 b 52 72 96 c 94 83.7 73 d 45 67 90.5 e 4 4.5 5 f 46 69 92 g 46 69 92 dim models tc533ax tc333ax tc233ax a b c d e f g e n w terminal connections control output measured v alue input relay output ssr drive output 12 vdc 10 12 + t h e r m o c o u p l e ( j , k , t , r , s ) rtd (pt100) 6 7 tc+ tc c o n n e c t t h e r m o c o u p l e s e n s o r a c c o r d i n g t o p o l a r i t y s h o w n . 6 7 8 rtd1 rtd2 rtd3 pt100 for 2-wire r td input short terminals 7 and 8 nc 3 4 5 no com f o r t c 5 3 3 a x selec tc533ax / tc233ax / tc33 3ax operating instructions r caution 7 8 9 10 6 tc /rtd1 tc /rtd2 rtd3 1 1 12 2 1 3 4 5 l (+) n ( ) no com ssr + - nc - + o p 2 9 3 - v 0 4 free datasheet http:///
8 9 tc+ tc 10 1 1 tc+ tc front p anel description 3. auto tuning: the auto-tuning function automatically computes and sets the proportional band (p), integral time (i), derivative time (d), ar w% and cycle time (cy .t) as per process characteristics. ! while auto-tune is in progress, lower display alternate shows a t & setpoint. ! lower display stops alternating between a t & setpoint at the completion of auto-tuning. ! i f t h e p o w e r g o e s o f f b e f o r e a u t o - t u n i n g i s completed, auto-tuning will be restarted at next power on. ! if auto-tuning is not completed after 3-4 cycles, the auto-tuning is suspected to fail. in this case, check the wiring & parameters such as the control action, input type, etc. ! carry out the auto-tuning again, if there is a change in setpoint or process parameters. calibra tion cer tifica te 5. manual reset (for pid control & i=0): after some time the process temperature settles at some point and there is a dif ference between the set te mp er at ur e & th e co nt ro ll ed te mp er at ur e. th is dif ference can be removed by setting the manual res et value equal & opposite to the of fset. s e t p o i n t t emp. o f f s e t m a n u a l r e s e t a d j u s t e d t i m e p r o p o r t i o n a l w i t h m a n u a l r e s e t t ime t emp. s e t p o i n t p r o p o r t i o n a l b a n d p i d - t i m e p r o p o r t i o n i n g w i t h a u t o r e s e t & r a t e t ime a t off 4. on/off control action (for reverse mode): the relay is on  up to the set temperature and cuts off' above the set temperature. as the temperature of the system drops, the relay is switched on' at a temperature slightly lower than the set point. hysteresis: the dif ference between the temperature at which relay switches on  and at which the relay switches off  is the hysteresis or dead band. set point overshoot hysteresis on on off output t emp. time reverse set point hysteresis off on o f f t emp. time output forward terminal connections control output control output measured v alue input measured v alue input relay output relay output ssr drive output ssr drive output t h e r m o c o u p l e ( j , k , t , r , s ) t h e r m o c o u p l e ( j , k , t , r , s ) rtd (pt100) rtd (pt100) c o n n e c t t h e r m o c o u p l e s e n s o r a c c o r d i n g t o p o l a r i t y s h o w n . c o n n e c t t h e r m o c o u p l e s e n s o r a c c o r d i n g t o p o l a r i t y s h o w n . for 2-wire r td input short terminals 9 and 10. for 2-wire r td input short terminals 7 and 8 f o r t c 2 3 3 a x f o r t c 3 3 3 a x nc 6 5 no com 7 nc 8 7 no com 9 12 vdc 12 13 + 12 vdc 16 17 + pt100 rtd1 rtd2 rtd3 8 9 10 pt100 rtd1 rtd2 rtd3 10 1 1 12 w arning: please check the power supply voltage and controllers output type ordered (with reference to the order code) before installation. t o view parameters on the same level. functions key press front keys description online t o view level 1 t o view level 2 t o view protection level t o view and change setpoint value press to view the setpoint. press + / key to change thesetpoint. programming mode t o increase or decrease the value of a particular parameter . note: the unit will auto exit programming mode after 30 seconds of inactivity . user guide user guide 1. display bias: this function is used to adjust the pv value in cases where it is necessary for pv value to agree with another recorder or indicator , or when the sensor cannot be mounted in correct location. 2. filter t ime constant the input filter is used to filter out quick changes that occur to the process variable in a dynamic or quick responding application which causes erratic control. the digital filter also aids in controlling processes where the electrical noise af fects the input signal. larger the value of ftc entered, greater the filter added and the slower the controller reacts to the process and vice versa. 3 1 2 r l (+) n ( -) no 1 2 3 4 5 6 7 co m 8 9 10 1 1 12 13 14 tc /r td 1 tc /r td 2 rt d3 nc s s r + - l (+) n (- ) no 1 2 5 4 6 7 8 9 com nc 10 1 1 12 13 14 15 16 17 18 tc /rt d1 tc /rt d2 rtd 3 s s r + - 3 ensure that the input sensor connected at the terminals and the input type set in the temperature controller configuration are the same. use only the correct thermocouple wire or compensating cable from the probe to instrument terminals avoiding joints in the cable if possible. failure to use the correct wire type will lead to inaccurate readings. + _ + _ press key for 3 seconds. press key for 3 seconds. press + keys for 3 seconds. or key once to view the next or previous function in operational menu. + to increase and + to decrease the function value. note: parameter value will not alter when respective level is locked. by pressing the or or + keys for 3 seconds. o r product is tested & calibrated by automatic technique. the calibration of this instrument is done as per following accuracy : for tc inputs: 0.25% of fs 1 for r & s inputs: 0.5% of f .s 2 ( 20 min of warm up time for tc input ) for r td inputs: 0.1% of fs 1 sources calibrated against: kusam-meco, model 405, sr .no.:104446 initial calibration is valid for 18 months after the month/y ear of manufacturing which is mentioned on order code label. o p e ra ti n g /1 1 0 3 / t c 5 3 3 a x / t c 2 3 3 a x / t c 3 3 3 a x / o p 2 9 3 -v 0 4 (p a g e 2 o f 3 ) 1 2 process-value (pv) / parameter name display set-value (sv) / parameter settingdisplay 1) displays a process value (pv). 2) displays the parameter symbols at parameter setting mode. 3) displays pv error conditions. (refer t able 2) 1) displays a set value (sv). 2) displays the parameter settings at parameter setting mode. 3 control output indication the led is lit when the control output is on t une 1 ) a u t o t u n e : l o w e r d i s p l a y a l t e r n a t e b e t w e e n a t & s e t p o i n t free datasheet http:///
opera tional menu r level 1 level 2 protection level display display default v alue default v alue default v alue range range range j/k/t/r/s/r td off/on unk/lck 1 to 400 unk/lck c/ f 0.0 to 99.9 min unk/lck m i n r a n g e o f s e n s o r s e l e c t e d t o s p . h 0 to 999 sec sp .l t o ma x ra ng e of s en so r se le ct ed aut/us.f 0.2 to10.0 sec 0.1 to 99.9 sec re/fd 0.1 to 99.9 pid/onf -19.9 to 19.9 1 to 100 % no/yes -19.9 to 19.9 display condition display condition display condition for cnt=onf f o r c n t = p i d & i = 0 description input type (refer t able 1) t une (refer user guide) lock setpoint proportional band lock level 1 t emperature unit integral time lock level 2 set point low limit derivative time set point high limit cycle time mode cycle time control action hysteresis control logic manual reset (refer user guide) anti reset windup % factory default (reset all) description description display bias (refer user guide) filter time constant (refer user guide) display t o increase/decrease setpoint: press + / keys. 1. locking parameters (l v1 or l v2 or sp) will not permit change in the value of respective level parameters. 2. continuos operation of + / keys for sp or other parameters makes update speed faster in 3 stages after 3 seconds. note range: sp .l to sp .h programming setpoint (online): default: 50 for cnt=pid configura tion instructions key functions  press once to view next parameter in configuration menu press for 3 sec to enter level 1 + or + allows the user to increase or decrease associated parameter value or or + t o ex it c on fi gu ra ti on m en u pr es s an y of t he se k ey s fo r 3 se c. + press for 3 sec to enter protection level for cnt=pid for cnt=pid for cnt=pid for cnt=pid for cnt=pid for cnt=pid input ranges (t able 1) p t1 0 0 c f j t f o r r t d f o r t h e r m o c o u p l e s e n so r b re a k / o ve r ra n g e c o n d iti o n s e n so r re ve rs e / u n d e r ra n g e c o n d iti o n o f f w he n an e rr or h as o cc ur ed , t he u pp er d is pl ay in di ca te s er ro r c od es a s gi ve n be lo w . in p u t m e a n in g c o n tr o l o u tp u t s ta tu s e rr o r error displa y (t able 2) -1 5 0 t o 8 5 0 -1 9 9 t o 9 9 9 r a n g e s r & s in p u t r a n g e s c -1 9 9 t o 7 5 0 f -1 9 9 t o 9 9 9 c -1 9 9 t o 4 0 0 f -1 9 9 t o 7 5 0 c 0 t o 9 9 9 f 3 2 t o 9 9 9 o f f selec controls pvt. ltd. (specifications are subject to change, since development is a continuous process) t elephone: +91-22-40394200 / 40394202 fax: +91-22-28471733t oll free: 1800 227 353 w ebsite: www .selec.com email: sales@selec.com press for 3 sec to enter level 2 k c -1 9 9 t o 9 9 9 f -1 9 9 t o 9 9 9 o p e ra ti n g /1 1 0 3 / t c 5 3 3 a x / t c 2 3 3 a x / t c 3 3 3 a x / o p 2 9 3 -v 0 4 (p a g e 3 o f 3 ) press key for 3 sec. press key for 3 sec. press + keys for 3 sec. note : at power on lower display shows (momentary) input type selected in level 1. power on press once to view previous parameter in configuration menu free datasheet http:///


▲Up To Search▲   

 
Price & Availability of TC333AX

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X